Self-Priming Pumps for Double Wall Tanks with Top Drain Lines

A double wall tank is usually emptied through a top drain line: a suction pipe that runs down inside the inner tank and out through the dome, so neither wall has a hole below the liquid. That means the pump has to pull the liquid up and over the top. Here is how much lift that takes and which pumps can do it.

We do not sell pumps. We build the tank and the top drain line, and we share this information to help you get a pump that suits your tank and chemical.

How a Top Drain Line Works With a Pump

Our top drain line is a Schedule 80 PVC or CPVC pipe that runs from just above the floor of the inner tank, up through a fitting on the dome, and down the outside of the tank to working height. It is built with:

  • Foot valve at the bottom of the suction pipe. It holds the line full of liquid when the pump stops, so the pump does not have to re-prime every time.
  • Capped tee at the top of the line. Remove the cap and fill the line with liquid to prime it.
  • Ball valve at working height to open and shut off the line.
  • Male camlock with dust cap for a quick pump or hose connection.
  • Welded pipe supports along the outside of the tank.

Once the line is full, it acts like a siphon: the liquid in the outside leg balances the liquid rising inside the tank. The hard part is getting it full in the first place, or getting it full again after it loses its prime. That takes a pump that can pull air out of the line and lift the liquid from the bottom of the tank over the top. That is a self-priming pump.

How Much Suction Lift Does Your Tank Need?

Pumps are rated for suction lift in feet of water. A heavier liquid is harder to lift, so multiply the height by the liquid’s specific gravity (SG) to get the lift in feet of water. Measure from the bottom of the tank to the top of the drain line:

Double wall tank (overall height) Water (1.0 SG) 1.5 SG liquid 1.9 SG liquid
1,000 gal (89″) 7.4 ft 11.1 ft 14.1 ft
2,000 gal (120″) 10 ft 15 ft 19 ft
5,000 gal (178″) 14.8 ft 22.3 ft 28.2 ft
6,000 gal (182″) 15.2 ft 22.8 ft 28.8 ft
10,000 gal (202″) 16.8 ft 25.3 ft 32 ft

Add a little for the pipe above the dome and for friction in the line. At sea level, atmospheric pressure can hold up at most 33.9 ft of water, and in practice most pumps top out near 25 ft. At altitude, take off about 1 ft of lift for every 1,000 ft of elevation. Hot liquids, and liquids that give off gas such as bleach, lift less.

If the number for your tank is more than your pump’s rated lift, keep the foot valve working and prime the line through the capped tee, or use one of the options under When the lift is too high.

Self-Priming Pumps That Work on a Top Drain Line

Pump type Typical lift Can it run dry? Good for
Air-operated double diaphragm (AODD) Up to about 20 ft wet, less when starting dry Yes Most chemical transfer. Runs on compressed air, so there is no electric motor at the tank. Plastic bodies (polypropylene, PVDF) with PTFE diaphragms are common.
Peristaltic (hose) pump Up to about 30 ft Yes Tall tanks, dosing, abrasive or thick liquids. Only the hose touches the liquid.
Self-priming centrifugal (including self-priming mag drive) About 20 ft of water No; fill the casing before the first start Higher flow transfer of water and thin chemicals
Diaphragm metering pump Limited; check the model Varies Feeding a chemical at a set rate. Choose a degassing head for bleach and peroxide.
Gear, rotary vane, progressive cavity Moderate No (most models) Oils, glycol and thicker liquids
Flexible impeller A few feet No Small transfers from short tanks only

Lift figures vary by model, size and condition. Check the pump maker’s curve for the suction lift at your flow.

Pumps to Avoid on a Top Drain Line

  • Standard centrifugal pumps cannot pull air out of a suction line. If the foot valve leaks or the line drains, the pump runs dry and stops moving liquid.
  • Standard magnetic drive (mag drive) pumps, the usual sealless chemical pump, are not self-priming, and running dry can ruin their bearings. Use the self-priming version if you want mag drive on a top drain line.
  • Booster and multistage pumps are built for liquid flowing in on its own, unless the maker rates the model for suction lift.

Those pumps all work well with gravity feed from a low sidewall outlet. See our gravity-fed pump guide for water and chemical tanks.

Setting Up the Pump

  • Keep the pump low and close. Set it at the camlock at working height, not up on the tank. The shorter the suction run, the better.
  • Don’t shrink the suction line. Use a hose or pipe at least as large as the drain line and the pump inlet, with as few bends as you can.
  • Keep the line airtight. A loose camlock gasket or cracked hose on the suction side lets air in, and the pump loses its prime.
  • Keep the foot valve working. It holds the prime between runs. If the pump has to re-prime every start, check it.
  • Vent the tank. Size the vent at least 1″ larger than the largest fill or outlet connection, so the pump can’t pull a vacuum on the inner tank. See tank vents.
  • Support the hose and pump. Don’t hang their weight on the drain line or a tank fitting; that can crack the fitting and voids the fitting warranty.
  • Match the wetted parts (body, diaphragms, seals) to the chemical with our chemical compatibility chart, and give the pump supplier the chemical, strength, temperature and SG.

When the Lift Is Too High

Tall tanks holding heavy chemicals (the 1.9 SG column above) can be past what a pump can lift. Options:

  • Prime and hold. Fill the line through the capped tee and rely on the foot valve. Once the line is full, the pump only has to keep it moving.
  • Push instead of pull. A submersible pump or a vertical immersion (sump-style) pump sits in the liquid, put in through the manway, so there is no suction lift.
  • A low outlet through both walls. If your site rules allow an outlet below the liquid, expansion joint outlets and through-wall fittings give the pump gravity feed.

Self-Priming Pump Questions

What is a self-priming pump?

A pump that can pull air out of its suction line and lift liquid from below the pump without being filled by hand each time. Diaphragm (AODD), peristaltic and self-priming centrifugal pumps are the common types.

Why does a double wall tank need a self-priming pump?

Most double wall tanks drain through a top drain line, so there is no hole in either wall below the liquid. The pump has to lift the liquid from the bottom of the tank up through the dome, and only a self-priming pump can do that on its own.

How high can a self-priming pump lift?

Most top out near 25 ft of water at sea level; the physical limit is 33.9 ft. Divide the pump’s rated lift by the liquid’s specific gravity for heavier liquids, and take off about 1 ft per 1,000 ft of elevation.

Can I use a mag drive pump on a double wall tank?

Only a self-priming mag drive model, or a standard one fed by gravity from a low outlet. A standard mag drive pump cannot lift liquid through a top drain line and can be damaged by running dry.

What keeps the top drain line primed?

The foot valve at the bottom of the suction pipe. It holds the line full of liquid between runs. The capped tee at the top lets you fill the line by hand if it ever loses its prime.

Does Bailiff sell pumps?

No. We build the double wall tank and its top drain line, with a camlock ready for your pump. This information is here to help you choose a suitable pump.

Bailiff Enterprises does not sell, size or warrant pumps. This page is general information to help you talk with a pump supplier. Your pump supplier and the pump maker’s instructions have the final word.