Federal Secondary Containment Rules for Storage Tanks

What the EPA’s oil spill (SPCC) rule and the federal hazardous waste tank rules require for secondary containment: how big it must be, how much freeboard for rain, when a concrete dike works, and the other ways to contain a tank. Every requirement below links to the government source.

Not legal advice. This is a plain-English summary of federal rules with links to the official text. State rules, local fire codes and your permits may be stricter. Your SPCC Plan preparer, a professional engineer or your regulator makes the final call.

Which Federal Rules Apply?

What you storeMain federal ruleSecondary containment requirement
Oil: fuel, lube and hydraulic oil, crude, synthetic and mineral oils, animal fats and vegetable oilsEPA Spill Prevention, Control, and Countermeasure (SPCC) rule, 40 CFR Part 112Containment for all areas with a potential for a discharge, plus sized containment for each bulk storage container (largest tank + freeboard for rain)
Hazardous waste in tanksRCRA tank system rules, 40 CFR 264.193 and 265.193An external liner, a vault or a double-walled tank, with leak detection
Acids, caustics, bleach and other chemicals that are not wasteUsually state rules, local fire codes and facility permitsVaries by state and city; many accept a double wall tank

Sources: EPA compliance advisory (PDF); 40 CFR 112.7; 40 CFR 265.193.

The EPA SPCC Rule (Oil)

Who it covers

The SPCC rule generally applies to a facility with an aggregate aboveground oil storage capacity greater than 1,320 U.S. gallons, or completely buried storage greater than 42,000 gallons, where there is a reasonable expectation of an oil discharge to navigable waters or adjoining shorelines. Only containers of 55 gallons or more are counted. (Source: EPA compliance advisory (PDF))

General containment for every area that could spill

Every regulated facility must provide “appropriate containment and/or diversionary structures or equipment.” The rule lists these methods for onshore facilities:

The entire containment system, walls and floor, must be able to hold oil and be built so that a discharge from the tank will not escape before cleanup. (Source: 40 CFR 112.7(c))

Sized containment for bulk storage containers

Bulk storage container installations must have a secondary means of containment for the entire capacity of the largest single container plus sufficient freeboard to contain precipitation, and diked areas must be sufficiently impervious to contain discharged oil. Mobile and portable containers need sized containment too. (Sources: 40 CFR 112.8(c)(2) and (c)(11); EPA, secondary containment for each container)

How Much Freeboard? The 25-Year, 24-Hour Storm

The SPCC rule does not write a number into “sufficient freeboard.” EPA’s position is that “the proper standard of ‘sufficient freeboard’ to contain precipitation is that amount necessary to contain a 25-year, 24-hour storm event.” EPA did not make that the rule standard because some facilities have trouble getting recent storm data, so the Plan preparer may use another method that still meets the requirement. (Source: EPA, bulk storage secondary containment FAQ)

The federal hazardous waste tank rules use the same storm. An external liner or vault must hold 100 percent of the largest tank and keep out run-on and rain, unless it has extra capacity to hold the precipitation from a 25-year, 24-hour rainfall event. (Sources: 40 CFR 265.193(e); 40 CFR 264.193(e))

To find your site’s 25-year, 24-hour rainfall depth, use the National Weather Service’s NOAA Atlas 14 Precipitation Frequency Data Server: pick your location and read the 24-hour row under the 25-year column.

Calculate it for your site: our secondary containment calculator looks up the 25-year, 24-hour rainfall for your address from NOAA Atlas 14 and gives the minimum dike wall height.

Worked example

One 5,000 gallon tank sits in a 20 ft × 20 ft concrete dike, and the 25-year, 24-hour rainfall at the site is 7 inches. Rain inside the dike: 20 × 20 × (7 ÷ 12) = 233 cubic feet × 7.48 = about 1,745 gallons. The dike must hold about 5,000 + 1,745 = 6,745 gallons below its top, not counting the space the tank itself takes up. That is why a fixed “110%” is often too small outdoors. A closed double wall tank keeps rain out of the containment space.

The 110% figure is common in industry and some state codes, but it is not written in the federal SPCC rule. Some states require more; Colorado, for example, has required 150% of the largest tank for oil and produced water tanks in designated setback locations. (Source: Colorado rule 604.c(2)G (PDF))

When Will a Concrete Dike Work?

A concrete dike or wall is one of the containment methods the SPCC rule names. It works when:

A dike makes the most sense when several tanks share one containment area. For one bulk tank outdoors, a double wall tank avoids rainwater management, takes less floor space and keeps a leak covered.

Other Types of Secondary Containment for Tanks

TypeWhere it is namedBest for
Double-walled tank (inner tank inside an outer tank)Hazardous waste tank rules list it as accepted containment, with leak detection (40 CFR 265.193(d))Single bulk tanks, outdoor tanks, corrosive and hazardous liquids
External liner40 CFR 265.193(d)Tank farms on lined pads
Vault40 CFR 265.193(d)Tanks inside concrete enclosures
Dikes, berms, retaining walls40 CFR 112.7(c)Several tanks sharing one area
Curbing, drip pans40 CFR 112.7(c)Small leaks at valves, pumps and fittings
Sumps, collection systems, culverts and gutters40 CFR 112.7(c)Directing spills to a remote catchment
Spill diversion and retention ponds40 CFR 112.7(c)Large sites with remote containment
Weirs, booms, sorbents40 CFR 112.7(c)Active response, not primary bulk containment
Containment basins and spill palletsA form of dike or drip pan under 40 CFR 112.7(c)Drums, totes and small tanks; see our containment basins

Double Wall Tanks Under the Federal Rules

Under the hazardous waste tank rules, double-walled tanks must be designed as an integral structure so that a release from the inner tank is contained by the outer shell, and must have a built-in continuous leak detection system able to detect a release within 24 hours or at the earliest practicable time. (Source: 40 CFR 265.193(e)(3)) EPA’s SPCC integrity testing guidance also covers double-walled and elevated containers, so plan to inspect them like any bulk container. (Source: EPA integrity testing fact sheet (PDF))

Bailiff double wall tanks are molded inner and outer tanks with fittings built for double wall service, and an interstitial leak detector can be added. See double wall tank sizes.

Oilfield and Elevated Tanks

Production sites, tank batteries, elevated tanks and Bureau of Land Management (BLM) rules on federal leases are covered on our oilfield tank containment and BLM rules page.

Questions

Does the EPA require 110% containment?

No federal SPCC rule states 110%. The rule requires containment for the entire capacity of the largest single container plus sufficient freeboard to contain precipitation, and EPA says the proper standard for that freeboard is a 25-year, 24-hour storm. Some states and local codes set their own percentages.

What is the EPA’s 24-hour rainfall standard for containment?

For oil storage under the SPCC rule, EPA considers the 25-year, 24-hour storm event the proper standard for sufficient freeboard. Federal hazardous waste tank rules also size liners and vaults for precipitation from a 25-year, 24-hour rainfall event. Local storm depths come from NOAA Atlas 14.

Will a concrete dike meet the rules?

It can. For oil, the dike must be sufficiently impervious, sized for the largest tank plus rain, and drained only through manual open-and-closed valves after the rainwater is inspected. For hazardous waste, concrete needs a compatible impermeable coating or lining and chemical-resistant water stops at joints.

Is a double wall tank accepted as secondary containment?

Federal hazardous waste tank rules list a double-walled tank as one of the accepted forms of secondary containment, along with an external liner and a vault, with leak detection between the walls. For oil and chemicals, confirm with your SPCC Plan preparer and local regulator.

Who has to follow the SPCC rule?

Generally, a non-transportation-related facility with more than 1,320 gallons of aboveground oil storage, counting containers of 55 gallons or more, where a discharge could reach navigable waters or adjoining shorelines.

Sources

  1. 40 CFR 112.7, General requirements for SPCC Plans, paragraph (c) — Electronic Code of Federal Regulations
  2. 40 CFR 112.8, SPCC requirements for onshore facilities, paragraphs (b) and (c)
  3. EPA, bulk storage secondary containment FAQ — U.S. Environmental Protection Agency
  4. EPA, secondary containment for each container — U.S. EPA
  5. EPA compliance advisory (PDF): Oil storage and the SPCC rule — U.S. EPA
  6. EPA SPCC Guidance for Regional Inspectors, Ch. 4 — U.S. EPA
  7. EPA integrity testing fact sheet (PDF) — U.S. EPA
  8. 40 CFR 265.193 and 40 CFR 264.193, Containment and detection of releases (hazardous waste tank systems)
  9. NOAA Atlas 14 Precipitation Frequency Data Server — National Weather Service, NOAA
  10. Colorado rule 604.c(2)G (PDF) — Colorado Oil and Gas Conservation Commission (state example)

Page reviewed November 2026. Regulations change; always check the current official text.