Home › Secondary Containment › Federal Rules
What the EPA’s oil spill (SPCC) rule and the federal hazardous waste tank rules require for secondary containment: how big it must be, how much freeboard for rain, when a concrete dike works, and the other ways to contain a tank. Every requirement below links to the government source.
| What you store | Main federal rule | Secondary containment requirement |
|---|---|---|
| Oil: fuel, lube and hydraulic oil, crude, synthetic and mineral oils, animal fats and vegetable oils | EPA Spill Prevention, Control, and Countermeasure (SPCC) rule, 40 CFR Part 112 | Containment for all areas with a potential for a discharge, plus sized containment for each bulk storage container (largest tank + freeboard for rain) |
| Hazardous waste in tanks | RCRA tank system rules, 40 CFR 264.193 and 265.193 | An external liner, a vault or a double-walled tank, with leak detection |
| Acids, caustics, bleach and other chemicals that are not waste | Usually state rules, local fire codes and facility permits | Varies by state and city; many accept a double wall tank |
Sources: EPA compliance advisory (PDF); 40 CFR 112.7; 40 CFR 265.193.
The SPCC rule generally applies to a facility with an aggregate aboveground oil storage capacity greater than 1,320 U.S. gallons, or completely buried storage greater than 42,000 gallons, where there is a reasonable expectation of an oil discharge to navigable waters or adjoining shorelines. Only containers of 55 gallons or more are counted. (Source: EPA compliance advisory (PDF))
Every regulated facility must provide “appropriate containment and/or diversionary structures or equipment.” The rule lists these methods for onshore facilities:
The entire containment system, walls and floor, must be able to hold oil and be built so that a discharge from the tank will not escape before cleanup. (Source: 40 CFR 112.7(c))
Bulk storage container installations must have a secondary means of containment for the entire capacity of the largest single container plus sufficient freeboard to contain precipitation, and diked areas must be sufficiently impervious to contain discharged oil. Mobile and portable containers need sized containment too. (Sources: 40 CFR 112.8(c)(2) and (c)(11); EPA, secondary containment for each container)
The SPCC rule does not write a number into “sufficient freeboard.” EPA’s position is that “the proper standard of ‘sufficient freeboard’ to contain precipitation is that amount necessary to contain a 25-year, 24-hour storm event.” EPA did not make that the rule standard because some facilities have trouble getting recent storm data, so the Plan preparer may use another method that still meets the requirement. (Source: EPA, bulk storage secondary containment FAQ)
The federal hazardous waste tank rules use the same storm. An external liner or vault must hold 100 percent of the largest tank and keep out run-on and rain, unless it has extra capacity to hold the precipitation from a 25-year, 24-hour rainfall event. (Sources: 40 CFR 265.193(e); 40 CFR 264.193(e))
To find your site’s 25-year, 24-hour rainfall depth, use the National Weather Service’s NOAA Atlas 14 Precipitation Frequency Data Server: pick your location and read the 24-hour row under the 25-year column.
One 5,000 gallon tank sits in a 20 ft × 20 ft concrete dike, and the 25-year, 24-hour rainfall at the site is 7 inches. Rain inside the dike: 20 × 20 × (7 ÷ 12) = 233 cubic feet × 7.48 = about 1,745 gallons. The dike must hold about 5,000 + 1,745 = 6,745 gallons below its top, not counting the space the tank itself takes up. That is why a fixed “110%” is often too small outdoors. A closed double wall tank keeps rain out of the containment space.
The 110% figure is common in industry and some state codes, but it is not written in the federal SPCC rule. Some states require more; Colorado, for example, has required 150% of the largest tank for oil and produced water tanks in designated setback locations. (Source: Colorado rule 604.c(2)G (PDF))
A concrete dike or wall is one of the containment methods the SPCC rule names. It works when:
A dike makes the most sense when several tanks share one containment area. For one bulk tank outdoors, a double wall tank avoids rainwater management, takes less floor space and keeps a leak covered.
| Type | Where it is named | Best for |
|---|---|---|
| Double-walled tank (inner tank inside an outer tank) | Hazardous waste tank rules list it as accepted containment, with leak detection (40 CFR 265.193(d)) | Single bulk tanks, outdoor tanks, corrosive and hazardous liquids |
| External liner | 40 CFR 265.193(d) | Tank farms on lined pads |
| Vault | 40 CFR 265.193(d) | Tanks inside concrete enclosures |
| Dikes, berms, retaining walls | 40 CFR 112.7(c) | Several tanks sharing one area |
| Curbing, drip pans | 40 CFR 112.7(c) | Small leaks at valves, pumps and fittings |
| Sumps, collection systems, culverts and gutters | 40 CFR 112.7(c) | Directing spills to a remote catchment |
| Spill diversion and retention ponds | 40 CFR 112.7(c) | Large sites with remote containment |
| Weirs, booms, sorbents | 40 CFR 112.7(c) | Active response, not primary bulk containment |
| Containment basins and spill pallets | A form of dike or drip pan under 40 CFR 112.7(c) | Drums, totes and small tanks; see our containment basins |
Under the hazardous waste tank rules, double-walled tanks must be designed as an integral structure so that a release from the inner tank is contained by the outer shell, and must have a built-in continuous leak detection system able to detect a release within 24 hours or at the earliest practicable time. (Source: 40 CFR 265.193(e)(3)) EPA’s SPCC integrity testing guidance also covers double-walled and elevated containers, so plan to inspect them like any bulk container. (Source: EPA integrity testing fact sheet (PDF))
Bailiff double wall tanks are molded inner and outer tanks with fittings built for double wall service, and an interstitial leak detector can be added. See double wall tank sizes.
Production sites, tank batteries, elevated tanks and Bureau of Land Management (BLM) rules on federal leases are covered on our oilfield tank containment and BLM rules page.
No federal SPCC rule states 110%. The rule requires containment for the entire capacity of the largest single container plus sufficient freeboard to contain precipitation, and EPA says the proper standard for that freeboard is a 25-year, 24-hour storm. Some states and local codes set their own percentages.
For oil storage under the SPCC rule, EPA considers the 25-year, 24-hour storm event the proper standard for sufficient freeboard. Federal hazardous waste tank rules also size liners and vaults for precipitation from a 25-year, 24-hour rainfall event. Local storm depths come from NOAA Atlas 14.
It can. For oil, the dike must be sufficiently impervious, sized for the largest tank plus rain, and drained only through manual open-and-closed valves after the rainwater is inspected. For hazardous waste, concrete needs a compatible impermeable coating or lining and chemical-resistant water stops at joints.
Federal hazardous waste tank rules list a double-walled tank as one of the accepted forms of secondary containment, along with an external liner and a vault, with leak detection between the walls. For oil and chemicals, confirm with your SPCC Plan preparer and local regulator.
Generally, a non-transportation-related facility with more than 1,320 gallons of aboveground oil storage, counting containers of 55 gallons or more, where a discharge could reach navigable waters or adjoining shorelines.
Page reviewed November 2026. Regulations change; always check the current official text.
Need containment?