Fittings & Options · Double wall

Options for Double Wall Tanks

A double wall tank is a tank inside a tank: if the inner (primary) tank leaks, the outer (secondary) tank holds the liquid. These options keep that containment intact and tell you when the inner tank has a problem.

OptionWhat it does
Interstitial leak detectorSounds an alarm if liquid gets into the space between the walls.
Top fill and top drain linesFill and empty the tank through the top, with no hole in either wall below the liquid. Recommended for double wall tanks.
Expansion joint outletsSidewall outlets that let the inner and outer tanks move independently.
Interstitial hose transfer fittingConnects an inner-tank outlet to the outer wall through a hose, so the fittings do not have to line up.
Through-wall couplings and fittingsWelded couplings and PVC or CPVC fittings that pass through both walls.

Interstitial leak detector

An interstitial leak detector warns you when the primary tank of a double wall tank leaks. A probe hangs to the bottom of the space between the inner and outer tanks; when it touches liquid, the detector sounds a horn, flashes a red strobe and can signal your control system. It mounts on a 2″ NPT fitting on top of the secondary tank, so nothing passes through the primary tank.

  • Early warning: finds a primary tank leak while the outer tank still holds the liquid.
  • Fail-safe probe: the system checks the probe constantly and alarms if it fails or is disconnected.
  • All-PVC probe: potted conductance probe that can be fully submerged.
  • Sound and light: 95 dB horn with a silence button and a flashing red strobe on the box.
  • Ties into your system: optional relay output for a PLC, control system or auto-dialer.
  • Simple install: connect power and the probe. It also works as a stand-alone high level alarm.
Interstitial leak detector alarm enclosure with red strobe for a double wall tank
Alarm enclosure with strobe.
ModelJWB Company LDA-1 Leakminder
Power110 VAC (24 VDC optional), under 1 A
EnclosureNEMA 4X, 10″ x 7″ x 3.5″
Probe and cableConductance type, all PVC, 19 ft cable
Alarms95 dB horn with silence; red strobe
Relay (optional)Form C, NO/NC, 5 A at 120 VAC
Connection2″ NPT with cable grip or conduit
OptionsUL approved version; relay output; 24 VDC power
WarrantyOne year from the manufacturer

Leak detector spec sheet (PDF)

Inside view of an interstitial leak detector control box
Inside view.
Conductance probe for a double wall tank leak detector
Probe.

Expansion joint outlets

The inner and outer tanks of a double wall tank move a little differently as they fill, empty and change temperature, so a sidewall outlet that is rigid through both walls can be strained. An expansion joint between the two walls takes up that movement.

When the space between the primary and secondary walls is too small for the length of the expansion joint, we add a welded flange to the outer tank and extend it to whatever length is needed to meet the face of the expansion joint. A blind flange or HDPE bolted cover is attached to the welded flange, and a bolted double flange is attached on the outside.

Expansion joint flange spec sheet (PDF)

Expansion joint and bolted flange on the outlet of a double wall tank
Expansion joint outlet.
Welded flange on the outer wall of a double wall tank
Welded flange on the outer wall.

Interstitial hose transfer fitting

Another way to bring a sidewall outlet through both walls is a hose transfer fitting. A bulkhead and elbow on the inner tank connect to a short hose in the space between the walls, which runs to an outlet fitting on the outer wall. Because the hose bends, the inner and outer fittings do not have to line up, and the two tanks can move without straining the connection.

Drawing of a 2 inch interstitial hose transfer fitting between the inner and outer walls of a double wall tank
2″ interstitial hose transfer assembly.

Hose transfer fitting drawing (PDF)