Fittings & Options · Level
We install four kinds of level indicator on our tanks: a reverse float gauge you can read from the ground, a sight gauge, an ultrasonic level transmitter for remote monitoring, and a high level switch for overfill alarms. Each one is installed at our plant in Willis, Texas, so the tank arrives ready to use.
| Indicator | How it reads | Power | Best for |
|---|---|---|---|
| Reverse float gauge | Orange indicator in a clear tube on the side of the tank | None | Reading the level at a glance, outdoors or with no power at the tank. Our standard level option. |
| Sight gauge | The liquid itself, in a clear PVC tube | None | Single wall tanks where you want to see the actual liquid. |
| Ultrasonic transmitter | 4-20 mA signal to a display, PLC or SCADA | 24 VDC loop | Remote monitoring, inventory and automatic fill control. Nothing touches the liquid. |
| High level switch | On/off contact when the liquid reaches a set height | Through your alarm or control circuit | Overfill alarms and pump shut-off. |
A reverse float gauge shows the level on the outside of the tank with no power and no electronics. A float rides on the liquid inside the tank, and a line runs from the float over a double pulley in the top fittings to an orange indicator inside a clear outer pipe on the side of the tank. As the level changes, the indicator moves in the clear pipe, so you can read it from the ground.
The reverse float is the default level indicator on our tanks. It needs a closed top, so it is not offered on open-top tanks.

A sight gauge is a clear PVC tube connected to the tank near the bottom and near the top, so the liquid in the tube stands at the same level as the liquid in the tank. It has a PVC ball valve at the top and bottom so the tube can be shut off or drained, and it is held by HDPE support arms. We build sight gauges in ½″ to 3″ tubing.
Because a sight gauge needs connections through the tank wall, we do not install them on double wall tanks; use a reverse float or ultrasonic transmitter there instead.

For remote monitoring we install a Flowline EchoSonic II ultrasonic level transmitter in a top fitting. It measures the distance to the liquid surface with sound, so nothing touches the chemical, and sends a two-wire, loop-powered 4-20 mA signal to a display, PLC, SCADA system or controller. A remote display can show the level in gallons at eye level or in a control room.
| Model | Measuring range | Tank connection |
|---|---|---|
| LU27 | 4″ to 9.8′ | 1″ NPT |
| LU23 | 8″ to 18.0′ | 2″ NPT |
| LU28 | 8″ to 26.2′ | 2″ NPT |
| LU29 | 8″ to 32.8′ | 2″ NPT |
We size the model to the tank height and keep the sensor clear of fill lines and other fittings so the beam has a clean path to the liquid.

A high level switch is a small float switch mounted near the top of the tank. When the liquid lifts the float, the switch changes state and can sound an alarm or shut off a fill pump before the tank overfills. Our standard switch is all PVDF (Kynar) for chemical resistance:

Not sure which level indicator you need?
Tell us the chemical, tank size and whether you need a remote signal, and we will recommend one and quote it installed. Request a quote · dmiller@plasticstoragetanks.com
Ultrasonic transmitter ranges and ratings are from Flowline’s EchoSonic II data sheet; high level switch ratings are from the switch manufacturer’s data sheet. Always confirm against the data sheet for the exact model supplied.